Allowable Current of the Wire
A.W.G. - mm Conversion Table
Construction of Conduct Twisted Wire
Construction of External Conduct (Shield)
Core Identification
Direct Current Conductor Resistance Cal
Flame Test Method
Physical Properties of Insulation Materials
°ü·Ã»çÀÌÆ®
The leading manufacturer of monitor, computer cable and LAN cable.
 


Å¿µÀüÀÚÁÖ½Äȸ»ç´Â ÃàÀûµÈ °æÇè°ú ±â¼ú°³¹ßÀ» ¹ÙÅÁÀ¸·Î ¸ð´ÏÅÍ, ÄÄÇ»ÅÍ, LAN ÄÉÀ̺íÀ» »ý»êÇÏ´Â Çѱ¹ÀÇ ¼±µµ ±â¾÷ÀÔ´Ï´Ù. Å¿µÀº ÄÉÀÌºí »ý»ê¿¡ ÀÖ¾î µðÀÚÀÎ ºÎÅÍ Ç°ÁúÀÎÁõ Á¦µµ±îÁö ¿Ïº®ÇÑ ÃÑüÀû ½Ã½ºÅÛÀ¸·Î ISO 9001 ÀÎÁõÀ» ȹ

  

Allowable Current of the Wire  


 ->Allowable Current Calculation Equation

 

 

  1.The allowable current of insulated wire is calculated as follows.
(JIS 168C) (Single core cable laid in air or duct)

l

Allowable current[A]

T1

Conduct max. allowable Temperature[°C] insulation heat resistant temperature

T2

Abient temperature(generally 40¡E)

r

Conduct effective resistance of wire at T1°C [¡ÍØ/cm]

r0

Conduct effective resistnace of wire at 20°C [¡ÍØ/cm]

¡Íá

Temperature coefficient of conductor resistance for copper wire 0.00393 for all wire 0.0040

Rth

Gross thermal resistance of insulation[ C*cm/W]

d1

Conductor outside dia.[mm]

d2

Insulation outside dia.[mm]

¨Ï&hibar;0

: Allowable current reduction rate when multiple of wire and laid

 

¡Íñ1: Unique thermal resistance of insulation

¡Íñ3: Surface radiation thermal resistance

[¡Écm/W]

[¡Écm/W]

Polyethylene

450

Materials shown

550 + 100d2(d2¡Â40)

PVC

600

in the left table

 

FEP

400

innersed braid

400 + 20d2(d2¡Â20)

TFE

450

include

              800(d2>20)

Nylon

450

 

 

 

Max. allowable temperature(°C)   Reffer to heat resistance of each material

General PVC

60

Heat Resistance PVC

75, 80, 90, 105

PE

75

FEP

200

  

2. The reduction rate must be applied when multiple of insulated wires are to be laid side by side Reduction rate for multiple laying in air(¨Ï&hibar;0)

 

3. When the base temperature(T2) is different from 40(30) °C, the conpensation factor for each temperature must be applied.

    Base temperature compensation factor

l'

Allowable current at the base temperature of T2

l

Allowable current at the base temperature of 40 °C

T1

Conductor max. temperature



 -> Allowable current of wire for internal wiring of electric equipmen

 The following current of wire for internal wiring of various electric equipment is as follows when one wire is installed in air

Normal Conductor Sectional Area §±

Allowable Current

PVC cord for appliances

Heat resistance PVC cord

PVC insulated wire for 600V electric equipment

0.75

7

8

10

1.25

12

14

13

2.0

17

20

18

3.5

23

28

26

5.5

35

42

36

8

-

-

46

14

-

-

68

22

-

-

95

30

-

-

116

38

-

-

135

50

-

-

159

60

-

-

185

80

-

-

225

100

-

-

262

Conductor max. allowable temperature

60

75

60

Ambient temperature

30

30

40



 -> Allowable Current Compensation Factor Table

 When the ambient temperature is different, multiply the following factor according to the temperature to calculate the allowable curren

Ambient Temperature ¡É

Factor

Vinyl cord for application

Heat resistance PVC cord

Vinyl insulated wire for 600V electric equipment

90

-

-

-

80

-

-

-

70

-

0.33

-

65

-

0.47

-

60

-

0.58

-

55

0.41

0.66

0.50

50

0.58

0.74

0.71

45

0.71

0.81

0.87

40

0.82

0.88

1.00

35

0.91

0.94

1.12

30

1.00

1.00

1.22

 

 



(ÁÖ)Å¿µÀüÀÚ. °æ±âµµ ½ÃÈï½Ã Á¤¿Õµ¿ 1269-6È£ (½ÃÈ­°ø´Ü 3³ª 107È£) 429-850, TEL. 031-499-5995 ~ 9, FAX. 031-498-3443